Назва: DEVELOPMENT OF A METHOD FOR ASSESSING THE RELIABILITY OF FIRE DETECTION IN PREMISES
Автори: Sadkovyi, Volodymyr
Pospelov, Boris
Rybka, Evgenіy
Kreminskyi, Borys
Yashchenko, Oleksandr
Bezuhla, Yuliia
Darmofal, Eleonora
Kochanov, Eduard
Hryshko, Svitlana
Kozynska, Iryna
Дата публікації: 2022
Видавництво: Sadkovyi, V., Pospelov, B., Rybka, E., Kreminskyi, B., Yashchenko, O., Bezuhla, Y., Darmofal, E., Kochanov, E., Hryshko, S., & Kozynska, I. (2022). Development of a method for assessing the reliability of fire detection in premises. Eastern-European Journal of Enterprise Technologies, 3(10 (117), 56–62. https://doi.org/10.15587/1729-4061.2022.259493
Бібліографічний опис: Sadkovyi, V., Pospelov, B., Rybka, E., Kreminskyi, B., Yashchenko, O., Bezuhla, Y., Darmofal, E., Kochanov, E., Hryshko, S., & Kozynska, I. (2022). Development of a method for assessing the reliability of fire detection in premises. Eastern-European Journal of Enterprise Technologies, 3(10 (117), 56–62. https://doi.org/10.15587/1729-4061.2022.259493
Короткий огляд (реферат): Abstract A fire in a building directly affects the lives of its occupants. Therefore, a safer environmental system that can minimize the damage caused by a fire occurring indoors needs to be developed. Recent studies on computer vision-based rapid fire detection methods aim to overcome the limitations of general fire detectors and prevent false alarms using advanced deep learning technology. However, studies considering the development of a video fire detection model for indoor usage and its implementation in an actual test room are lacking. We developed a computer vision-based early fire detection model (EFDM) using an indoor closed-circuit television (CCTV) surveillance. The proposed EFDM derives the fire detection time through actual fire tests. The possibility and necessity of using fire detectors indoors is confirmed by comparing the results with the fire detection times of a general fire detector. The developed model achieves a recall, precision, and mAP0.5 performance of 0.97, 0.91, and 0.96, respectively. The fire recorded in the indoor fire video test dataset was detected within 8 s. The possibility of fire detection from three combustibles according to Underwriters Laboratories (UL) 268 B is confirmed via experimentation. A difference of up to 307 s is observed when the fire detection times of the EFDM and general fire detectors are compared. The usable range is confirmed by detecting a fire within 1 s of the maximum visible range of the CCTV. The proposed method can help contribute to the reduction of unfortunate property damages or casualties caused by a fire.
URI (Уніфікований ідентифікатор ресурсу): http://repositsc.nuczu.edu.ua/handle/123456789/16704
Розташовується у зібраннях:Кафедра управління та організації діяльності у сфері цивільного захисту

Файли цього матеріалу:
Файл Опис РозмірФормат 
R y b k a.pdf694,46 kBAdobe PDFПереглянути/Відкрити


Усі матеріали в архіві електронних ресурсів захищені авторським правом, всі права збережені.