Будь ласка, використовуйте цей ідентифікатор, щоб цитувати або посилатися на цей матеріал:
http://repositsc.nuczu.edu.ua/handle/123456789/17880
Повний запис метаданих
Поле DC | Значення | Мова |
---|---|---|
dc.contributor.author | Ковальов, Андрій Іванович | - |
dc.contributor.author | Отрош, Юрій Анатолійович | - |
dc.contributor.author | Васильченко, Олексій Володимирович | - |
dc.contributor.author | Адаменко, Н.И | - |
dc.date.accessioned | 2023-06-15T20:27:56Z | - |
dc.date.available | 2023-06-15T20:27:56Z | - |
dc.date.issued | 2018 | - |
dc.identifier.citation | Matec Web of Conferences | uk_UA |
dc.identifier.uri | http://repositsc.nuczu.edu.ua/handle/123456789/17880 | - |
dc.description.abstract | Abstract. The problem of estimation of fire resistance of steel frame structures with intumescent coatings is considered. It implies that both physical properties of a covering (its thickness and structure) and mechanical properties of a metal structure change critically at heating. All above changes should be considered to maintain the standard values of fire resistance of a construction at calculation. Usually, known technical characteristics of fire resistance of intumescent coverings are used for estimation of fire resistance of steel structures with intumescent coverings. Importance of taking into account the influence of strength loss time at heating of a steel structure on calculation of fire resistance limit of system “intumescent fireproof coating – steel structure” is shown in the article. On an example of calculation of heating time to the critical temperature of steel columns and beams protected by intumescent coating, it is shown that own heating time of steel structures before they lose strength makes 10 to 16 % from a settlement limit of fire resistance. This fact should be considered at the forecast of fire resistance of steel frame structures with intumescent coatings. | uk_UA |
dc.language.iso | en | uk_UA |
dc.publisher | Харків,НУЦЗ України | uk_UA |
dc.relation.ispartofseries | ;230 | - |
dc.title | Feature of fire resistance calculation of steel structures with intumescent coating | uk_UA |
dc.type | Article | uk_UA |
Розташовується у зібраннях: | Кафедра пожежної профілактики в населених пунктах |
Файли цього матеріалу:
Файл | Опис | Розмір | Формат | |
---|---|---|---|---|
37 - Стаття.pdf | 323,15 kB | Adobe PDF | Переглянути/Відкрити |
Усі матеріали в архіві електронних ресурсів захищені авторським правом, всі права збережені.