Please use this identifier to cite or link to this item: http://repositsc.nuczu.edu.ua/handle/123456789/12316
Title: Influence of the Fire Temperature Regime on the Fire-Retardant Ability of Reinforced-Concrete Floors Coating
Authors: Andrii Kovalov, Yurii Otrosh, Oleg Semkiv, Volodymyr Konoval, Oleksandr Chernenko
Keywords: hollow-core reinforced-concrete floors, fire-resistant quality, fire-retardant coating, fire-retardant ability, temperature regime of the fire
Issue Date: 2020
Publisher: Trans Tech Publications Ltd
Series/Report no.: 1006;87-92
Abstract: In the paper, the tests have been analysed for fire-resistant quality of the hollow-core reinforced-concrete floors with fire-retardant plaster covering under standard temperature regime of the fire. Using the methodology for determining the characteristics of fire-retardant coatings ability for reinforced-concrete floors, the dependences have been obtained of the fire-retardant coating thickness from the concrete protective layer of a hollow-core reinforced-concrete floor for a fire resistance limit of 180 minutes with a temperature regime of hydrocarbon fire and a tunnel curve according to the Netherlands standards (RWS). It has been concluded about the minimum required thickness of the studied fire-retardant coating to provide the required fire resistance limit of a hollow-core reinforced-concrete floor under the indicated fire regimes
URI: http://repositsc.nuczu.edu.ua/handle/123456789/12316
Appears in Collections:Кафедра пожежної профілактики в населених пунктах

Files in This Item:
File Description SizeFormat 
MSF.1006.87.pdf365,5 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.