Please use this identifier to cite or link to this item: http://repositsc.nuczu.edu.ua/handle/123456789/21157
Title: STUDY OF FIRE TEMPERATURE MODES IN HORIZONTAL CABLE TUNNELS DEPENDING ON PARAMETERS AND FIRE LOAD
Other Titles: ДОСЛІДЖЕННЯ ТЕМПЕРАТУРНИХ РЕЖИМІВ ПОЖЕЖІ У ГОРИЗОНТАЛЬНИХ КАБЕЛЬНИХ ТУНЕЛЯХ В ЗАЛЕЖНОСТІ ВІД ЇХНІХ ПАРАМЕТРІВ ТА ПОЖЕЖНОГО НАВАНТАЖЕННЯ
Authors: Степаненко, Віталій Олександрович
Нуянзін, Олександр Михайлович
Keywords: cable
tunnel
electrical
networks
power consumption
switching
computing experiment
fire resistance, fire resistance
Issue Date: 21-Jun-2024
Publisher: Черкаськи інститут імені Героїв Чорнобиля НУЦЗ України
Citation: Том 8 № 1 (2024): Збірник наукових праць Черкаського інституту пожежної безпеки імені Героїв Чорнобиля Національного університету цивільного захисту України «Надзвичайні ситуації: попередження та ліквідація» 2024, с. 139-150.
Abstract: Based on the results of the work, the dependences describing the maximum temperature inside the cable tunnel during a fire, the duration of a fire in a certain local area of the cable tunnel, and the time to reach the maximum temperature inside the cable tunnel during a fire were obtained from the fire load, the cross-sectional area ofthe tunnel, and the speed of movement of air masses inside.In one of the CFD software complexes, a mathematical model of the cable tunnel, similar to the real one, was created. A computational experiment was conducted. Modeling, as a method of scientific research, makes it possible to conduct all the necessary experiments on determining the temperature regimes of fire in cable tunnels without performing materially expensive and time-consuming field experiments on models.Based on the results of the computationalexperiment and field tests, adequacy criteria were calculated (Student's t-test, Cochran's Q-test, Fisher's F-criterion). Based on the analysis, the adequacy of the used mathematical models was investigated.A full factorial experiment was designed and conducted. According to its results, regressions of the maximum temperature inside the cable tunnel during a fire, the duration of a fire in a certain local area of the cable tunnel, and the time of reaching the maximum temperature inside the cable tunnel during a fire were obtained.The temperature regime of the fire in cable tunnels with different sizes, aerodynamic parameters and fire load was determined, as well as the dependence on the specified parameters of the temperature regime of the fire
URI: http://repositsc.nuczu.edu.ua/handle/123456789/21157
Appears in Collections:Том 8 номер 1 (2024)

Files in This Item:
File Description SizeFormat 
STUDY OF FIRE TEMPERATURE MODES IN HORIZONTAL CABLE TUNNELS.pdfОсновна стаття1,33 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.