Title: DETERMINATION OF VARIOUS TYPES ELECTRIC LAMPS PARAMETERS IN EMERGENCY MODES OF OPERATION
Other Titles: ВИЗНАЧЕННЯ ПАРАМЕТРІВ ЕЛЕКТРИЧНИХ ЛАМП РІЗНИХ ТИПІВ ПРИ АВАРІЙНИХ РЕЖИМАХ РОБОТИ
Authors: Kalchenko, Yaroslav
Afanasenko, Kostiantyn
Oliinyk, Volodymyr
Borsuk, Olena
Kostyrka, Olesya
Keywords: lamp temperature
overvoltage
undervoltage
fire hazard
Issue Date: Jun-2025
Publisher: НУЦЗ України
Series/Report no.: 41;
Abstract: Studies have been conducted to determine the temperature of electric lamps of various types in emergency modes of operation of power grids, namely overvoltage. Graphs of the dependence of the temperature of the bulb of incandescent lamps, arc mercury lamps and LED lamps on the voltage ap-plied to them. Mathematical models of the value of the heating temperature of the bulb of the electric incandescent lamp, the arc mercury lamp and the LED lamp are obtained depending on the time. It is determined that the temperature of the bulb of the incandescent electric lamp increases exponentially and stabilizes after about 300 seconds. The temperature of an arc mercury lamp also varies exponential-ly, but, compared to an incandescent lamp, it is not so fast, but stabilizes after about 600 seconds. It is determined that in emergency modes of operation, the temperature of incandescent lamps and arc mer-cury lamps may exceed the normative values of temperature groups, as a result of which, when used in environments where explosive gases or vapors are present, they can become a source of ignition and lead to explosion or ignition of these substances. It is determined that the temperature of the LED lamp changes according to the linear law and after 300 seconds stops growing. Temperature dependencies of different elements of the LED lamp are built depending on the electric voltage applied to it. It was found that the driver, namely the power control chip, heats up most when the LED electric lamp is op-erating. It is determined that when the electric voltage decreases, the power control chip heats up more, but not significantly. It was found that the LED lamp is the best from the point of view of fire safety, since it has the lowest temperature, and also the change in the voltage of the electrical network reacts the least, which is explained by its design and principle of operation.
URI: http://repositsc.nuczu.edu.ua/handle/123456789/26873
ISSN: 2524-0226
Appears in Collections:Кафедра пожежної і техногенної безпеки об'єктів та технологій

Files in This Item:
File Description SizeFormat 
ПНС 41 Кальченко Афанасенко та ін.pdf1,83 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.