Будь ласка, використовуйте цей ідентифікатор, щоб цитувати або посилатися на цей матеріал:
http://repositsc.nuczu.edu.ua/handle/123456789/27343| Назва: | Studying Fire Hazard of Premises of a Mobile Communications Base Station. |
| Автори: | FESHCHUK, Yurii NIZHNYK, Vadym TSYHANKOV, Andrii MELNYK, Valentyn SHARIPOVA, Dariya |
| Ключові слова: | fire hazard fire-fighting system premises of a mobile communications base station flame propagation temperature |
| Дата публікації: | 2025 |
| Бібліографічний опис: | Institute of Scientific Research on Civil Protection of the National University of Civil Protection of Ukraine, 60 Centralna St., Dmytrivka village, Buchanskyi district, Kyiv region, Ukraine, 2025. |
| Короткий огляд (реферат): | The need to study the fire hazard of typical premises of a mobile communications base station was substantiated, in particular, regarding the feasibility of equipping it with an automatic (self-contained) fire-fighting system. Criteria for assessing the fire hazard of a mobile communications base station were developed. It was experimentally established that the greatest fire hazard in the premises of a mobile communications base station was related to the following devices: Alarm Box switching panel, input and distribution board, internal air conditioner unit and 12 V 100 A#2 batteries. Moreover, the latter two ones contribute to the spread of fire inside the premises. During the ignition of the 12 V 100 A#2 batteries, it was established that the surface of the outer wall further heated to a temperature of 80 °C, which did not exceed the critical one. Thus, the fire did not spread beyond the premises. It was established that equipping the premises of a mobile communications base station with a fire-fighting system in order to prevent the fire spreading beyond its boundaries was unreasonable. |
| URI (Уніфікований ідентифікатор ресурсу): | http://repositsc.nuczu.edu.ua/handle/123456789/27343 |
| Розташовується у зібраннях: | Кафедра пожежно-рятувальної та фізичної підготовки |
Файли цього матеріалу:
| Файл | Опис | Розмір | Формат | |
|---|---|---|---|---|
| Studying_Fire_Hazard_of_Premises_of_a_Mobile_Commu.pdf | 1,55 MB | Adobe PDF | Переглянути/Відкрити |
Усі матеріали в архіві електронних ресурсів захищені авторським правом, всі права збережені.