Назва: Studying Fire Hazard of Premises of a Mobile Communications Base Station
Автори: Feshchuk, Yurii
Nizhnyk, Vadym
Tsyhankov, Andrii
Melnyk, Valentyn
Ключові слова: fire hazard
premises of a mobile communications base station
flame propagatio
temperature
fire-fighting system
Дата публікації: 10-лис-2025
Короткий огляд (реферат): The need to study the fire hazard of typical premises of a mobile communications base station was substantiated, in particular, regarding the feasibility of equipping it with an automatic (self-contained) fire-fighting system. Criteria for assessing the fire hazard of a mobile communications base station were developed. It was experimentally established that the greatest fire hazard in the premises of a mobile communications base station was related to the following devices: Alarm Box switching panel, input and distribution board, internal air conditioner unit and 12 V 100 A#2 batteries. Moreover, the latter two ones contribute to the spread of fire inside the premises. During the ignition of the 12 V 100 A#2 batteries, it was established that the surface of the outer wall further heated to a temperature of 80 °C, which did not exceed the critical one. Thus, the fire did not spread beyond the premises. It was established that equipping the premises of a mobile communications base station with a fire-fighting system in order to prevent the fire spreading beyond its boundaries was unreasonable
URI (Уніфікований ідентифікатор ресурсу): http://repositsc.nuczu.edu.ua/handle/123456789/27876
Розташовується у зібраннях:Науково-дослідний центр нормативно-технічного регулювання

Файли цього матеріалу:
Файл Опис РозмірФормат 
Studying_Fire_Hazard_of_Premises_of_a_Mobile_Commu (1).pdf1,55 MBAdobe PDFПереглянути/Відкрити


Усі матеріали в архіві електронних ресурсів захищені авторським правом, всі права збережені.